Installation requirements for vortex flowmeters for steam

Time: 2024-09-20
Equipment Configuration:vortex flowmeters for steam

Steam vortex flowmeter is a measuring instrument for steam trade settlement, and its importance in measurement is self-evident.

Project Overview

Steam vortex flowmeter is a measuring instrument for steam trade settlement, and its importance in measurement is self-evident. In order to ensure the long-term stable operation of the steam vortex flowmeter, users should pay attention to the following points during installation.

1. Straight pipe section: The length of the upstream pipe of the vortex flowmeter should be a straight pipe section of equal diameter not less than 10D. If the installation site allows, it is recommended that the upstream straight pipe section be 20D and the downstream straight pipe section be 5D.

2. Requirements for piping: The inner diameter of the upstream and downstream piping at the installation point of the vortex flowmeter is the same as the inner diameter of the flowmeter. It must be installed horizontally on the pipe (the pipe inclination is within 5°). During installation, the flow rate The gauge axis should be concentric with the pipeline axis and the flow direction should be consistent.

3. Requirements for bypass pipes: In order to ensure that the normal use of the medium is not affected during maintenance of the steam vortex flowmeter, stop valves should be installed on the front and rear pipes of the flowmeter, and a bypass pipe should be set up. . The flow control valve should be installed downstream of the flow meter. When the steam vortex flow meter is used, the stop valve installed upstream must be fully open to avoid unstable flow in the upstream part of the fluid.

4. Requirements for the external environment: The steam vortex flowmeter is best installed indoors. When it must be installed outdoors, sun protection, rain protection, and lightning protection measures must be taken to avoid affecting the service life.

5. Installation location: The flow meter should be installed in a location that is easy to maintain and free from strong electromagnetic interference and heat radiation.

6. Requirements for installation and welding: welding with a flow meter is not allowed. Before installing the vortex flowmeter, the pipeline should be cleaned of debris such as debris, welding slag, stones, dust, etc. It is recommended to install a filter with a 5-micron mesh upstream to block droplets and sand. It is best to use equal diameter pipes (or bypass pipes) instead of flow meters to purge the pipes. The user also provides a pair of standard flanges welded to the front and rear pipes.

7. Sealing gasket: When installing the flow meter, the sealing gasket between the flanges cannot be recessed into the pipe to prevent interference with normal flow measurement.

8. Grounding requirements: The steam vortex flowmeter should be reliably grounded and cannot be shared with the ground wire of the strong current system.

9. When storing a used vortex flowmeter, the residual liquid and adhesion inside should be completely cleaned. Also, pay attention to sealing the power interface to prevent moisture.

10. If there is a problem with the steam vortex flowmeter, please contact the manufacturer in time. Non-professionals should not blindly repair it by themselves.

Supmea Measurement and Control is a professional flowmeter manufacturer that has been committed to the research and development, production and service of flowmeters for many years. In order to ensure the correct installation of the steam vortex flowmeter, Supmea Measurement and Control provides on-site or telephone guidance and installation services. In addition, Supmea Measurement and Control has also developed a LUB anti-vibration vortex flowmeter. Its circuit board is equipped with a DSP signal processing circuit and anti-vibration algorithm, and is equipped with a mature piezoelectric crystal sensor. After long-term field testing and operation, its performance is reliable. Even under complex working conditions, LUB anti-vibration vortex flowmeter can effectively identify the signal generated by the flowmeter body and the interference signal generated by vibration and perform shielding processing to achieve accurateEnsure stable operation.

For more questions about the selection, installation, and debugging of vortex flowmeters, please feel free to contact Supmea Measurement and Control~

Related Cases

The magnetic inductive flowmeter industry, these are successful cases with comparable and reference value.

Please Fill In Your Request And We Will Contact You As Soon As Possible!

Whatsapp
Inquiry
Top