Metal tube float flowmeter common failure how to solve?

Time: 2024-07-19
Equipment Configuration:metal tube float flowmeter

Any flowmeter in use, will encounter some failures, for the metal tube float flowmeter of certain failures, the owners of how to solve it?

Project Overview

This article metal tube float flowmeter manufacturers give the following points, I hope it can help you.

1、No live display

  • 1)Check that the wiring is correct.
  • 2)Check that the power supply is correct.
  • 3)Reinstall the LCD module and check the contact is not solid.
  • 4)For multi-wire power supply check that terminals 12 and 13 are not connected to an ammeter or short-circuited.

2、No current output

  • 1)First look at the wiring to see if it is correct.
  • 2)LCD whether there is a display, if there is no output display, mostly bad output tube, need to replace the circuit board.
  • 3)Loss of calibration value. Due to E2PROM failure, resulting in the loss of instrument calibration data, will also cause no output current, the current will remain unchanged. Solution: Available data recovery operation, if it does not work, you can first set the data in password 2000, and then set the data in password 2008, the method is to push the pointer calibration by hand from RP - 100% of the data.

3、On-site LCD total display 0 or full scale

  • 1)Check the Set Range, Zero parameters in the 2000 code. It is required that ZERO should be less than the value of SPAN, and the two values should not be equal.
  • 2)Check whether the sampling data up, push the pointer by hand to see the sampling value changes, if there is no change, generally for the circuit board sampling circuit failure, need to replace the circuit board.

4、Incorrect alarm

  • 1)Check that the deviation setting d value is not too large.
  • 2)Check the size of the alarm value setting in the SU.
  • 3)Is the logic function correct in the FUN function. the HA-A indicates the upper limit positive logic.

5、If the LCD barcode indicates correctly and the output has no action, you can check whether the external power supply and the negative pole of the external power supply are connected to the negative pole of the instrument power supply.

6、Faulty circuit board, replace circuit board.

7、Incorrect accumulated pulse output

  • 1)Check that the alarm value of the one that selects the accumulated pulse output is set to zero.
  • 2)Faulty circuit board, replace circuit board.

Supmea produces metal tube float flowmeter for many years, if you encounter any problems in the process of metal tube float flowmeter selection, installation, use, maintenance, feel free to contact Supmea staff, we help you answer.